ICM Controls ICM102F Delay on Make Timer with .03-10 Minute Adjustable Time Delay, Universal 18-240 VAC, 6″ Wire Leads
- Universal voltage operation
- Higher 1.5 amp power rating
- Knob-adjustable time delays
- Works with anticipator-type thermostats
- One model replaces many in field
- Ideal for compressor staging
- Simple 2-wire hookup
- 6″ Wire Leads
SPECIFICATIONS
- Voltage: 18-240 VAC
- 1.5 amps
- 15 amp inrush
- 40 mA holding current
- Frequency: 50/60 Hz
- Adjustable delay: .03-10 minutes (1.8-600 seconds)
- Voltage drop: 2.5 V @ 1.5 amps
- Dimensions 2″ x 2″
REPLACES
- Supco: TD69W
- Wagner/DiversiTech: ADM-2
MODE OF OPERATION
When power is applied to the input, the time delays begins. After the time delay is complete, the load energizes and remains energized as long as power is applied. The control is reset by removing power during or after the time delay period. The ICM102 provides thermostat interruption protection, even in the presence of a trickle current.
Reviews
There are no reviews yet.